QO® and Homeline® Load Centers and Enclosures Class 1100Catalog1100CT05012007 CONTENTS Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page QO® Circuit Breakers and Load Centers . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 QO®, QOM2 and Q-Frame Enclosed Circuit Breakers . . . . . . . . . . . . . . . 34 Homeline® Circuit Breakers and Load Centers . . . . . . . . . . . . . . . . . . . . . 40 QO® and Homeline® Load Centers and EnclosuresTable of Contents TABLE OF CONTENTS Product Description 3 Features 3 QO® Catalog Number Description 4 General information and Application Data 5 Service 5 Ratings 5 Branch Circuit Breakers 5 Indoor Enclosures (Type 1) 6 Indoor Covers 6 Rainproof Enclosures (Type 3R) 6 Bolt-On Hubs 6 Class CTL 7 Phasing 7 Line Lugs 7 Neutral Assemblies 7 Single Phase, 2 16 Circuits, 30 125 A, Fixed Mains 8 Single-Phase,12 42 Circuits, 100 225 A, Convertible Mains 9 Special Purpose 11 Generator Panels 12 Three-Phase, 3 4 2 Circuits, 60 22 5 A, Convertible or Fixed Mains 13 Single-Phase, 12 42 Circuits, 300 400 A, Fixed Mains 15 Accessories 16 Technical Information 19 Grounding Bar Kits 19 Main Lugs and Main Circuit Breakers Ratings 20 Dimensions and Knockouts 26 QO 1-Phase and 3-Phase Label Samples 28 29 Wiring Diagrams 30 NOTE: For information on Replacement Parts with specific part numbers, go to www.schneider-electric.us, click on Product FAQ’s, enter the device catalog number, click SEARCH, then look for the information required
2 © 2007 Schneider Electric All Rights Reserved 03/2007 QO® and Homeline® Load Centers and Enclosures Product Description PRODUCT DESCRIPTION QO® Circuit Breaker Load Centers from Square D® are Underwriters Laboratories (UL) Listed panelboards. They are designed to meet residential, commercial, and industrial requirements to protect electrical systems, equipment, and people
Features Single- or three-phase construction 30 400 A main lug or main circuit breaker ratings 2 4 2 circuit indoor or outdoor versions Flush or surface mounting Aluminum bus construction on fixed mains panels Service entrance equipment capable panels Straight-in wiring to minimize service cable installation Convertible mains to meet changing job site requirements Standard 22/10 k AIR series rating on main circuit breaker panels, QO® Circuit Breaker Load Center increasing application capability 65 k AIR ratings for main lugs panels for industrial applications 65 k AIR rating with optional main circuit breaker on three-phase panels for industrial applications Shielded one-piece plated copper bus construction on convertible mains panels, an industry exclusive for protection and performance Single captive screw interior mounting on indoor panels to ease removal Split branch neutral for clutter-free wiring Top or bottom feed by rotating convertible mains panels 180 degrees Top or bottom feed for three-phase convertible panels by removing main circuit breaker and rotating panel 180 degrees Combination slot/square drive neutral, ground, and cover screws for positive drive and improved torque Three grounding bar mounting locations for ease of wiring Automatic flush adjustment cover to speed installation Tangential main service knockouts that eliminate offsets Equipment grounding bar included with main lug load centers Covers sold separately Provisions for door lock on convertible mains panel covers Two branch circuit breaker twistouts that are factory removed for easier installation of circuit breakers Side hinge doors on outdoor convertible main panels Outdoor panel covers lockable with padlock Manual and automatic transfer switch capability 303/2007 © 2007 Schneider Electric All Rights Reserved QO® and Homeline® Load Centers and EnclosuresCatalog Number Description CATALOG NUMBER DESCRIPTIONQO® Load CentersNumber Segment Character Description QO® 1 3040 L 200 G — — QO® UL and NOM ListedLoad Center Family CQO CSA® Certified Blank or 1 = SinglePhase 1 3 = ThreeSpaces / Circuits 3040 M Main circuit breaker MX Main circuit breaker for Automatic Transfer SwitchMains Type L Main lugs U Universal mains (studs only)Amperes Blank Purchase separately G IncludedGrounding Bar N Neutral installed T Factory-installed Blank Purchase cover separately C Combination flush / surface indoor cover DF Flush cover with door DS Surface cover with doorCover F Flush cover R Rainproof RB Rainproof for B hub S Surface cover CU Copper bussing FT Feed-thru lugs GP Generator panelSpecial Construction NM Non-metallic enclosure R Generator receptacle WG Wide gutter riser panel QO® Circuit Breakers Number Character Description QO® 1 15 — Segment QO Full Size Brand QOT Tandem Number of Poles Amperes Blank 10,000 AIR EPD 30 mA equipment ground fault protection GFI Ground fault circuit interruption HID For use on high intensity discharge lighting systems High magnetic trip circuit breakers are recommended for HM applications where high initial inrush current may occur Device Name K Key operated PL Remote control switching capability SWN Switch neutral common trip VH 22,000 AIR AFI Arc fault circuit interruption CAFI Combination arc fault circuit interruption4 © 2007 Schneider Electric All Rights Reserved 03/2007 QO® and Homeline® Load Centers and Enclosures General Information and Application Data GENERAL INFORMATION AND APPLICATION DATA Circuit breaker load centers for use on electrical systems are UL Listed under File E-6294 (panelboards) and meet Federal Specifications W-P-115c, Type 1, Class 2 for use in government housing. Select from QO, QOT, QO-PL, QO-GFI (UL Class A ground fault protection), QO-AFI (arc fault circuit interrupter), QO-CAFI (combination arc fault interrupter), or QO-EPD (30 mA equipment ground fault protection) branch circuit breakers
Service 120 Vac, 1φ2W 240/120 Vac delta, 3φ4W 120/240 Vac, 1φ3W 240 Vac corner grounded delta, 3φ3W 240 Vac delta, 3φ3W 48 Vdc maximum (1φ convertible main 208Y/120 Vac, 3φ4W lug 12 4 2 circuit only) Ratings Main Lugs Main Circuit Breaker Single-Phase 30 400 A 100 4 00 A QO® Circuit Breaker Load Center Three-Phase 60 225 A 100 2 25 A Branch Circuit Breakers 10,000 AIR 1-pole, 10 70 A QO 2-pole, 10 12 5 A 3-pole, 10 10 0 A QOT 1-pole, 15 20 A 1-pole, 15 30 A QO-EPD 2-pole, 15 60 A QO QO QO 1-pole, 15 30 A 1-Pole 2-Pole QO-EPD 1-Pole QO-GFI 3-Pole 2-pole, 15 60 A QO-AFI 1-pole, 15 20 A QO-CAFI 1-pole, 15 20 A 1-pole, 15 50 A QO-HID 2-pole, 15 50 A 3-pole, 15 30 A 1-pole, 10 20 A, 30 A QO-PL 2-pole, 10 60 A QO-PLILC 3-pole, 15 60 A 2-wire, 10 50 A QO-SWN 3-wire, 10 50 A QOK 1-pole, 10 30 A QO-GFI QO-GFI QO-CAFI 1-Pole 22,000 AIR 1-Pole 2-Pole QO-AFI 1-Pole QO-VHGFI 1-pole, 15 30 A 1-pole, 15 30 A QO-VH 2-pole, 15 12 5 A 3-pole, 15 10 0 A 2-pole, 150 A 1 QOB-VH 3-pole, 110 150 A 1 42,000 AIR QOH 2-pole, 40 12 5 A 65,000 AIR 1-pole, 15 30 A QO-PL 2-Pole QH 2-pole, 15 30 A 3-pole, 15 30 A 1 For use with 300 A and 400 A load centers only. Requires PK3CA QOK, 1-Pole QO-SWN, 1-Pole mounting kit, ordered separately
503/2007 © 2007 Schneider Electric All Rights Reserved QO® and Homeline® Load Centers and EnclosuresGeneral Information and Application Data Indoor Enclosures (Type 1) Welded sheet steel with knockouts at top, bottom, back, and sides Finish: gray baked enamel, electrodeposited over cleaned, phosphatized steel Most 100 225 A indoor enclosures are 14.25 in. (362 mm) wide (see Dimensions and Knockouts on page 26) 300 A and 400 A indoor enclosures are 20 in. (508 mm) wide Top or bottom feed by rotating enclosure Indoor Covers Doors to cover circuit breaker handles, except on 2 4, 4 8, 6 12 , and 8 16 circuit models Shutter-type twistouts Flush and surface covers available, sold separately QO130M150 Flush covers have automatic flush adjustment Field-installed door lock provisions available on most covers QOFP filler plates available for all covers QOM1FP filler plates available for 100 1 25 A convertible load center covers QOM2FP filler plates available for 150 2 25 A convertible load center covers Q2FP filler plates available for 3-phase load center covers Triple lead cover screws for fast cover installation Indoor Cover Rainproof Enclosures (Type 3R) Complete enclosure includes interior trim and door Welded, galvannealed steel Finish: gray baked enamel, electrodeposited over cleaned, phosphatized, galvannealed steel RB devices have provisions for interchangeable bolt-on hub Top-centered rainproof mounting boss on the back of the enclosure simplifies installation and saves time Stainless steel door latch on the enclosure provides secure closure and maximum durability Convertible main panels are side-hinge door devices Allow 1.25 in. (32 mm) on the left side for the door to open QO140M200RB Side-hinged door provides full wiring access without door removal Bolt-On Hubs Hubs available from 0.75 in. (19 mm) to 4 in. (102 mm) conduit size No gasket required with hubs from 0.75 in. (19 mm) to 2.50 in. (64 mm) when used on RB type load centers Bolt-On Hubs6 © 2007 Schneider Electric All Rights Reserved 03/2007 QO® and Homeline® Load Centers and Enclosures General Information and Application Data Class CTL Class CTL load centers are UL Listed Circuit breaker mounting rails have slots to accept tandem circuit breakers, on specified load centers Meets paragraph 408.35 of the 2005 National Electrical Code® (NEC®) Phasing Load centers have distributed phase bussing Most branch circuit breakers can be mounted in any position Line Lugs All lugs suitable for 75 °C copper or aluminum wires (see Main Lugs and Main Circuit Breaker Ratings on page 20) Main lugs and main circuit breaker load centers have wire binding screw Tandem circuit breaker mounts on rails. torque values on the wiring diagrams and circuit breaker labels Neutral Assemblies All lugs suitable for copper or aluminum wire (see Main Lugs and Main Circuit Breaker Ratings on page 20) Branch neutral terminals suitable for one #14 #4 AWG copper or one #12 #4 AWG aluminum wire Three #14 1/0 AWG copper or #14 #6 AWG aluminum terminals provided on 12 42 circuits, 100 225 A load centers Suitable lugs provided on the neutrals for termination of the grounding conductor All unused neutral terminals may be used to terminate bare or green equipment grounding conductors when the load center is used as service equipment: Branch Circuit Breaker one or two #14 # 12 AWG copper one or two #12 # 10 AWG aluminum Neutral assemblies accept copper or aluminum wire
703/2007 © 2007 Schneider Electric All Rights Reserved QO® and Homeline® Load Centers and EnclosuresGeneral Information and Application Data Single Phase, 2–16 Circuits, 30–125 A, Fixed Mains UL Listed File E-6294 Suitable for use as service equipment 75 °C wire rating (see Technical Information on page 20) Federal Specification W-P-115c, Type 1, Class 2 CSA Certified File LL-89066-21 For other CSA certified load centers, see Supplemental Digest 174
Short Circuit Current Rating QO24L70S UL short circuit current rating depends on lowest interrupting rating of circuit breaker installed (see Technical Information on page 20) Interior Tin plated aluminum bus Tin plated copper bus is an available option on 6 12 and 8 16 circuit load centers Tin plated copper bus is standard on 4 8 circuit load centers Mains Factory-installed main lugs Top mains positioning only Top or bottom feed A backfed main circuit breaker can be field-installed in 4 8 , 6 12 and 8 16 load centers using the PK2MB retaining kit Cover QO816L100DS Flush- or surface-mounted cover included with load centers A cover with a door is an available option on 6 1 2 and 8 16 circuit load centers QO148L125GF8 © 2007 Schneider Electric All Rights Reserved 03/2007 QO® and Homeline® Load Centers and Enclosures General Information and Application Data Single-Phase, 12–42 Circuits, 100–225 A, Convertible Mains UL Listed File E-6294 Federal Specification W-P-115c, Type 1, Class 2 Suitable for use as service equipment 75 °C wire rating (see Technical Information on page 20) Short Circuit Current Rating Main lugs: up to 65,000 AIR (depends on lowest interrupting rating of Main Circuit Breaker branch circuit breakers installed) Main circuit breaker: 22,000 AIR standard 22,000 AIR main circuit breaker kits (refer to page 10 and Technical Information on page 20) Interior Shielded, one-piece tin plated copper bus Removable interior with single, captive mounting screw Split branch neutral with up to 50% more terminations than required Multiple mounting locations for equipment grounding bar kits: left, right, and bottom Main lugs load centers have equipment grounding bar kits included (not Main Lug factory-installed) Mains Factory-installed main lugs convertible to main circuit breaker Load Center Amperage Main Circuit Breaker Kit Amperage 125 50 125 150 100 15 0 200 100 20 0 225 100 22 5 Factory-installed main circuit breaker convertible to main lugs Main Circuit Breaker Amperage Main Lug Kit Amperage Load Center Amperage 100 125 100 125 125 125 150 225 150 200 225 200 225 225 225 Top or bottom mains positioning. Rotate entire load center 180 degrees
903/2007 © 2007 Schneider Electric All Rights Reserved QO® and Homeline® Load Centers and EnclosuresGeneral Information and Application Data Single-Phase, 12–42 Circuits, 100–225 A, Convertible Mains, Continued Covers Flush and surface covers sold separately Flush covers have spring-loaded interior trim for automatic flush adjustment Positive action, easy-open door latch Main Lugs Kits Field-installable in main circuit breaker or main lugs load centers QOL125 kit for use in 100 125 A load centers QOL225 kit for use in 150 225 A load centers Main Circuit Breaker Kits Field-installable in main lugs or main circuit breaker load centers 50 2 25 A main circuit breaker kit is 22,000 AIR series rated with 10,000 Cover AIR branch circuit breakers Field-Installable Main Circuit Breaker (Convertible Main Load Centers Only) Use with 22,000 AIR Main Circuit Lug Wire Size 2 Convertible Lug Torque Breaker Ampere Main Circuit AWG/kcmil Load Center lb-in. / N•m Rating 1 Breaker Al or Cu Mains Rating QOL125 Kit QOM1 Frame Size 50 100 125 A QOM50VH 60 100 125 A QOM60VH 70 100 125 A QOM70VH 80 100 125 A QOM80VH 50 lb-in
#12 2/0 90 100 125 A QOM90VH (6 N•m) 100 100 125 A QOM100VH QOL225 Kit 110 125 A QOM110VH 125 125 A QOM125VH QOM2 Frame Size 3 4 100 150 225 A QOM2100VH 125 150 225 A QOM2125VH 150 150 225 A QOM2150VH 250 lb-in
#4 30 0 175 200 225 A QOM2175VH (28 N•m) 200 200 225 A QOM2200VH 225 225 A QOM2225VH 1 Do not exceed the load center mains rating
QOM1 2 Main Frame Size Wire range listed for QOM circuit breaker kits is the wire range of that circuit breaker. To find 50–125 A out maximum wire size permitted in a particular load center per UL, see Main Wire Size AWG/kcmil on page 20
3 Add suffix 1021 for shunt trip
4 Add suffix 8041 for control wire taps
QOM2 Main Frame Size 100–225 A10 © 2007 Schneider Electric All Rights Reserved 03/2007 QO® and Homeline® Load Centers and Enclosures General Information and Application Data Special Purpose Recreational Vehicle and Manufactured Housing Load Centers UL Listed (File E-6294) and CSA Certified (LL89066-14) Single-phase, 2- and 3-wire Factory-installed equipment grounding bar Covers included with load centers Load Centers with Covers QO2L30TTS Combination flush/surface cover included with load centers Equipment grounding bar included on main lug load centers Top or bottom feed on incoming service by rotating complete load center 180 degrees Convertible main load centers Non-Metallic Load Center UL Listed Suitable for use as service equipment Side-hinge door device 10,000 AIR rating Single-phase, 2- and 3-wire Factory-installed grounding bar Cover included with load center QO130M150 Knockouts in bottom endwall, side and back Main Circuit Breaker with Feed-Thru Lugs Available rainproof enclosure only Side hinge door devices Allow 1.25 in. (32 mm) on the left side for the door to open 125, 150, and 200 A mains rating 125, 150, and 200 A feed-thru lugs Space for up to 8 single-pole circuit breakers QO24L60NRNM QO1816M200FTRB 1103/2007 © 2007 Schneider Electric All Rights Reserved QO® and Homeline® Load Centers and EnclosuresGeneral Information and Application Data Generator Panels Generator Panel Manu al Transfer Connects utility and standby power to installed branch circuits Includes two factory-installed 2-pole main circuit breakers tied together with a mechanical interlock 30 A and 60 A main circuit breaker versions Supply up to 8 branch circuits using tandem circuit breakers Available indoor enclosure only Cover with door included Generator Panel Automatic Transfer QO48M60DSGP QO® load center platform construction Automatic transfer from utility to back-up power source Transfer cycle less than 10 seconds Indoor and outdoor enclosures 120 / 240 Vac single-phase 150, 200 and 225 A main circuit breaker 42 circuit maximum construction, indoor, 28 circuit maximum outdoor 125 A maximum branch feeder connection to an alternative energy source Service entrance rated Manual override capability Easy removal of interior and transfer switch for rough in wiring 5-year limited warranty Compatible with standard load center field-installable accessories Riser Panels Offset interior provides ample wire gutter space for high rise applications Factory-installed main lugs (125 A), convertible to main circuit breaker with standard QOC cover and optional Mono-Flat cover QO® Intelligent Load Center Factory-installed main lugs (200 A), convertible to main circuit breaker when used with QOC cover only Available in 12 to 40 circuits Indoor only Optional Mono-Flat® cover available for both 125 A and 200 A panels (sold separately) Wide Gutter12 © 2007 Schneider Electric All Rights Reserved 03/2007
QOfi Catalog Number Description 4 General information and Application Data 5 Service 5 Ratings 5 Branch Circuit Breakers 5 Indoor Enclosures (Type 1) 6 Indoor Covers 6 Rainproof …
Homeline breakers are cheaper, and QO breakers cost $10 but come with extra features such as Vis-Trip Indicator. Homeline breakers only cost $5 and are the perfect option if you don’t need to handle large electrical loads. Both Homeline and QO breakers are efficient and reliable, but it can be difficult to choose between them.
You can use QO breakers with CSED devices, QO load centers, and NQOD panel boards, and they are highly compatible. The main appeal of QO breakers is that they are rated for 240 volts and can handle heavy appliances. However, the wide variety of options means that you can find single-pole QO breakers if you only need them for electrical outlets.
Similar in many ways to the Square D Homeline, the Qo offers breaker protection to your electrical system. The biggest difference between the two is that the Qo comes in options up to 3-pole in space and can be used for commercial applications. Moreover, there is a visi-trip indicator that indicates which breaker has been tripped.
An Overview of the Square D Homeline The Homeline is a single-pole breaker meant for residential use. These breakers are meant to be 1 inch per pole space within your central breaker. The Homeline does come in 2-pole breaker options.